X
Troubleshooting ]
- 117 -
HWE07150
GB
1. Error
Code
Abnormal bus voltage rise (Detail code 109)
2. Error
definition and error detection method
If Vdc 830V is detected during inverter operation.
3. Cause, check method and remedy
(1) Different voltage connection
Check the power supply voltage on the power supply terminal block (TB1).
(2) INV board failure
If the problem recurs, replace the INV board.
In the case of 4220: INV board
In the case of 4225: Fan board
Refer to section - 6 - "Inverter" under part [4] "Trouble shooting principal parts" for error codes related to the
inverter.(page 172)
1. Error
Code
Logic error (Detail code 111)
2. Error
definition and error detection method
H/W error
If only the H/W error logic circuit operates, and no identifiable error is detected.
3. Cause, Check method and remedy
In the case of 4220
In the case of 4225
Refer to section - 6 - "Inverter" under part [4] "Trouble shooting principal parts" for error codes related to the
inverter.(page 172)
4220
4225
4220
4225
Cause
Check method and remedy
(1)
External noise
(2)
INV board failure
Refer to
X
[4] - 6 - (2) [1].
Cause
Check method and remedy
(1)
External noise
(2)
Fan board failure
Refer to
X
[4] - 6 - (2) [6].
Summary of Contents for City Multi PFAV-P500VMH-E
Page 1: ......
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 37: ... 28 ...
Page 39: ... 30 ...
Page 49: ... 40 ...
Page 55: ... 46 ...
Page 59: ... 50 ...
Page 61: ... 52 ...
Page 65: ... 56 ...
Page 67: ... 58 ...
Page 73: ... 64 ...
Page 75: ... 66 ...
Page 95: ... 86 ...
Page 107: ... 98 ...
Page 195: ... X Troubleshooting 186 HWE07150 GB ...
Page 197: ... 188 ...
Page 242: ......