II
Restrictions ]
- 27 -
HWE07150
GB
[5] Restrictions on Pipe Length
(1) End branching
1. Selection of refrigerant branch kit
Select an optional branch kit from the following table. (The kits include a set of branches for the liquid pipe and gas pipe.)
* Be sure to carry out installation in accordance with the installation manual of the outdoor branch kit.
2. Selection of each section of refrigerant pipe (floor-standing type)
(1) Between the outdoor first distributor and the indoor unit (C)
(2) Between the outdoor units and first distributor (A and B)
Unit: m [ft]
Operation
Pipe sections
Allowable length of
pipes
Length
Between outdoor units
A+B+C
10 [32] or less
Total pipe length (L) from the outdoor unit to the
farthest indoor unit
A(B)+C
150 [492] or less
Height
difference
Between indoor and outdoor units
H
50 [164] or less
(40 [131] or below if
outdoor unit is below in-
door unit)
Between outdoor units
h
0.1[0.3] or less
Set Name
Outdoor unit configuration
Branch Kit Name
P500
P250 (2)
CMY-Y100VBK2
Indoor Model
Connected Outdoor Model
Liquid Pipe Size (mm) [inch]
Gas Pipe Size (mm) [inch]
P500
P250
P250
ø15.88 [5/8"]
ø28.58 [1-1/8"]
Connected Outdoor Model
Liquid Pipe Size (mm) [inch]
Gas Pipe Size (mm) [inch]
P250
ø9.52 [3/8"]
ø22.2 [7/8"]
Outdoor unit
Indoor unit
L
H
h
First gas distributor
First liquid distributor
C
B
A
Note1 Install the pipe that connects the branch pipe and the outdoor units in
the way that it has a downward inclination toward the branch pipe.
Provide a trap on the pipe (gas pipe only) within 2 m from the
joint pipe if the total length of the pipe that connects the joint
pipe and the outdoor unit exceeds 2 m.
Downward inclination
To indoor unit
To indoor unit
To indoor unit
Trap
(gas pipe
only)
To indoor unit
Upward inclination
2m
2m Max.
Summary of Contents for City Multi PFAV-P500VMH-E
Page 1: ......
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 37: ... 28 ...
Page 39: ... 30 ...
Page 49: ... 40 ...
Page 55: ... 46 ...
Page 59: ... 50 ...
Page 61: ... 52 ...
Page 65: ... 56 ...
Page 67: ... 58 ...
Page 73: ... 64 ...
Page 75: ... 66 ...
Page 95: ... 86 ...
Page 107: ... 98 ...
Page 195: ... X Troubleshooting 186 HWE07150 GB ...
Page 197: ... 188 ...
Page 242: ......