- 42 -
Filter Sign Reset
[Circulating Water
Exchange Sign Reset]
(*6)
BV_xxxx12
INACTIVE : RESET
ACTIVE : Void
• Reset the filter sign of the group that detects filter sign
[ON(ACTIVE)] from BMS. (*2)
After doing so, check that the filter sign of the group turns to
OFF(INACTIVE) on BMS.
Prohibition On Off
BV_xxxx13
INACTIVE : Permit
ACTIVE : Prohibit
• Prohibit the remote controller (ON/OFF) of the specific
group from BMS.
After doing so, check that the remote controller (ON/OFF) of
the group turns to (ACTIVE) via the remote controller.
• Permit the remote controller (ON/OFF) of the specific
group from BMS.
After doing so, check that the remote controller (ON/OFF) of
the group turns to (INACTIVE) via the remote controller.
Prohibition Mode
BV_xxxx14
INACTIVE : Permit
ACTIVE : Prohibit
• Operation/checking object is the same as the steps of
remote controller (operation mode), but the checking method
is the same as the steps of remote controller (ON/OFF).
Prohibition Filter
Sign Reset
[Prohibition Circulating
Water Exchange Sign
Reset] (*6)
BV_xxxx15
INACTIVE : Permit
ACTIVE : Prohibit
• Operation/checking object is the same as the steps of
remote controller (filter sign reset), but the checking method
is the same as the steps of remote controller (ON/OFF).
Prohibition Set
Temperature
BV_xxxx16
INACTIVE : Permit
ACTIVE : Prohibit
• Operation/checking object is the same as the steps of remote
controller (set temperature), but the checking method is the
same as the steps of remote controller (ON/OFF).
M-NET
Communication
State
BI_xxxx20
INACTIVE: Normal
ACTIVE: Error
• Disconnect M-NET transmission line which is connected
to BAC-HD150 or PAC-YG50ECA.
After doing so, check that the M-NET communication status
of all groups turns to Error (ACTIVE) on BMS. (*3)
• Connect M-NET transmission line to BAC-HD150 or
PAC-YG50ECA.
After doing so, check that the M-NET communication status
of all groups turns to Normal (INACTIVE) on BMS.
System Forced Off
BV_xxxx21
BV_999921
INACTIVE: Reset
ACTIVE: Execute
• Perform a forced stop of the system of the specific group
from BMS.
After doing so, check that the air conditioner stops on BMS.
Air Direction Setup
MO_xxxx22
01 : Horizontal
02 : Downblow 60%
03 : Downblow 80%
04 : Downblow 100%
05 : Swing
• Change the air direction of the specific group from BMS.
After doing so, check that the air direction of the group
renews the direction using system controller or remote
controller.
Air Direction State
MI_xxxx23
01 : Horizontal
02 : Downblow 60%
03 : Downblow 80%
04 : Downblow 100%
05 : Swing
• Change the air direction of the specific group using
system controller or remote controller.
After doing so, check that the air direction of the group
renews the direction on BMS.
Set Temp Cool
AV_xxxx24
°F/°C
• Make a setting of set room temperature for cooling of the
specific group from BMS.
After doing so, check that the set room temperature for
cooling of the group renews the temperature using system
controller or remote controller.
• Change the set room temperature for cooling of the
specific group using system controller or remote
controller.
After doing so, check that the set room temperature for
cooling of the group renews the temperature on BMS.
Set Temp Heat
AV_xxxx25
°F/°C
• Make a setting of set room temperature for heating of the
specific group from BMS.
After doing so, check that the set room temperature for
heating of the group renews the temperature using
system controller or remote controller.
• Change the set room temperature for heating of the
specific group using system controller or remote
controller.
After doing so, check that the set room temperature for
heating of the group renews the temperature on BMS.
Control item
Object
Status
Steps
Result
WT05542X04.book Page 42 Wednesday, July 3, 2013 12:13 PM