- 32 -
7.3
Step - 1 Initial setting for air conditioning system
Make the initial settings for air conditioning system using Setting Tool.
(1) Installing the Setting Tool software
Install the Setting Tool program on a PC, and set the IP address. (Refer to the Instruction Book that came with Setting Tool for
installation and setting method.)
(2) Connecting the Setting Tool
Disconnect the LAN1 cable connected to BACnet
®
of BAC-HD150.
Use additional HUB to connect BAC-HD150 and Setting Tool.
Connect the LAN2 cable that is connected to BACnet
®
to the additional HUB.
(3) Data setting
Make the settings for the air conditioning system related items and IP address of BAC-HD150 by using Setting Tool.
The following table shows setting items. (Refer to the Instruction Book that came with Setting Tool for setting method.)
No.
Main tab
Sub tab
Setting item
1
System Settings
Basic System
All setting items
2
M-NET
All setting items
3
Expansion Controller
No settings required
4
Group Settings
Group
All setting items
5
LOSSNAY
All setting items
CAUTION
If IP address of BAC-HD150 overlaps any of the addresses that are assigned to other devices, communications
cannot be performed properly via BAC-HD150 or other devices. Check the address before setting.
MEMO :
When settings are changed by using Setting Tool after the initial settings have been completed, it is not necessary
to disconnect the LAN1 cable from BACnet
®
.
㩷
HUB
HUB
LAN2
LAN1
HUB
BACnet
®
M-NET
M-NET
M-NET
BAC-HD150
Step-1
Outdoor unit
Outdoor unit
Indoor unit
Indoor unit
ME remote controller
ME remote controller
System controller
Setting Tool
LOSSNAY
LOSSNAY
Connect the
LAN2 cable.
Disconnect the
LAN1 cable.
BMS