- 20 -
3.9
Error Code
The following table shows the details in the Present_Value property of the Error Code (MI_xxxx04).
No.
MI_xxxx04
PV
State
M-NET Error Code
1
1
Normal
8000 or all the codes except
No.2 ~ No.9
2
2
Other errors
0000 ~ 0999
6000 ~ 6499, 6750 ~ 6779
3
3
Refrigeration system fault
1000 ~ 1999
4
4
Water system error
2000 ~ 2999
5
5
Air system error
3000 ~ 3999
6
6
Electronic system error
4000 ~ 4999
7
7
Sensor fault
5000 ~ 5999
8
8
Communication error
6500 ~ 6749, 6780 ~ 6999
9
9
System error
7000 ~ 7999