- 10 -
3.3
Objects
Supported object list is shown below.
: Supported
: Not supported
*1: Inside the brackets indicates control item for BU or AU group. (Refer to section 1.2 Restrictions/Cautions.)
*2: Use “Set Temp Auto” to control temperatures in the Auto mode for the dual set point indoor unit groups, using one
temperature setting. To use two different temperature settings, use “Set Temp Cool” and “Set Temp Heat” instead.
Object type
Abbreviation
Support
Control item
Notes
Accumulator
23
Analog Input
0
AI
Room Temp
[Water Temp]
*1
Analog Output
1
Analog Value
2
AV
Set Temp
Set Temp Cool
Set Temp Heat
Set Temp Auto
Set High Limit Setback Temp
Set Low Limit Setback Temp
[Set Water Temp]
*1
*2
Averaging
18
Binary Input
3
BI
On Off State
Alarm Signal
Filter Sign
[Circulating Water Exchange Sign]
M-NET Communication State
Expansion Controller Communication State
*1
Binary Output
4
BO
On Off Setup
Binary Value
5
BV
Filter Sign Reset
[Circulating Water Exchange Sign Reset]
Prohibition On Off
Prohibition Mode
Prohibition Filter Sign Reset
[Prohibition Circulating Water Exchange Sign Reset]
Prohibition Set Temperature
System Forced Off
*1
Calendar
6
Command
7
Device
8
DEV
Device object of BAC-HD150
Event Enrollment
9
File
10
Group
11
Life Safety Point
21
Life Safety Zone
22
Loop
12
Multi-state Input
13
MI
Error Code
Operational Mode State
Fan Speed State
Air Direction State
Ventilation Mode State
Air To Water Mode State
Multi-state Output
14
MO
Operational Mode Setup
Fan Speed Setup
Air Direction Setup
Ventilation Mode Setup
Air To Water Mode Setup
Multi-state Value
19
Notification Class
15
CLS
Object for Event notification
Program
16
Pulse Converter
24
Schedule
17
Trend Log
20