- 19 -
3.8
Event service specifications
The following table shows the supported notifications for each object.
The Event notification is used to notify the Alarm and Event. The COV notification is used to notify the change of Present
Value.
Selection of “Confirmed” or “Unconfirmed” can be made for each notification target.
: Notification is settable using setting data
: Notification is not settable
*1: Inside the brackets indicates control item for BU or AU group. (Refer to section 1.2 Restrictions/Cautions.)
Control item
Object ID
Event
notification
COV
notification
Notes
On Off Setup
BO_xxxx01
On Off State
BI_xxxx02
Alarm Signal
BI_xxxx03
Error Code
MI_xxxx04
Operational Mode Setup
MO_xxxx05
Operational Mode State
MI_xxxx06
Fan Speed Setup
MO_xxxx07
Fan Speed State
MI_xxxx08
Room Temp
[Water Temp]
AI_xxxx09
*1
Set Temp
[Set Water Temp]
AV_xxxx10
*1
Filter Sign
[Circulating Water Exchange Sign]
BI_xxxx11
*1
Filter Sign Reset
[Circulating Water Exchange Sign Reset]
BV_xxxx12
*1
Prohibition On Off
BV_xxxx13
Prohibition Mode
BV_xxxx14
Prohibition Filter Sign Reset
[Prohibition Circulating Water Exchange Sign Reset]
BV_xxxx15
*1
Prohibition Set Temperature
BV_xxxx16
M-NET Communication State
BI_xxxx20
System Forced Off
BV_xxxx21
BV_999921
Air Direction Setup
MO_xxxx22
Air Direction State
MI_xxxx23
Set Temp Cool
AV_xxxx24
Set Temp Heat
AV_xxxx25
Set Temp Auto
AV_xxxx26
Set High Limit Setback Temp
AV_xxxx27
Set Low Limit Setback Temp
AV_xxxx28
Ventilation Mode Setup
MO_xxxx35
Ventilation Mode State
MI_xxxx36
Air To Water Mode Setup
MO_xxxx37
Air To Water Mode State
MI_xxxx38
Expansion Controller Communication State
BI_xx9981
Notification Class
CLS_xxxxxx
Device
DEV_xxxxxx
WT05542X04.book Page 19 Wednesday, July 3, 2013 12:13 PM