- 13 -
: Controllable
: Not controllable
*1: Outdoor unit errors will be detected as the errors of the entire groups that IC, KIC, AIC, LC, and FU belong to, to which the
outdoor units are connected.
SC and RC errors will not be treated as BAC-HD150 errors.
*2: The settable temperature ranges are as follows.
(The following tables show only the representative ranges. The settable range varies with the models.)
*3: Includes the FU (OA processing units) that are configured in the group but not interlocked with the indoor units.
*4: In the “ON/OFF”, “Mode”, “Set temp” prohibit functions, only “ON/OFF” prohibit function can be used with K-control indoor
units. “Mode” or “Set temp” prohibit functions synchronize with the state of “ON/Off ” prohibit function.
*5: K-control indoor unit does not support “Filter Sign Reset” prohibit function.
*6: Not available depending on the type of units that are connected.
*7: Inside the brackets indicates control item for BU or AU group. (Refer to section 1.2 Restrictions/Cautions.)
Control item
Object type
Instance
number
Model group
Note
IC Group *3
LC Group
BU.AU
Group
On Off Setup
BO
xxxx01
On Off State
BI
xxxx02
Alarm Signal
BI
xxxx03
Error Code
MI
xxxx04
*1
Operational Mode Setup
MO
xxxx05
Operational Mode State
MI
xxxx06
Fan Speed Setup
MO
xxxx07
Fan Speed State
MI
xxxx08
Room Temp
[Water Temp]
AI
xxxx09
*7
Set Temp
[Set Water Temp]
AV
xxxx10
*2, *7
Filter Sign
[Circulating Water Exchange Sign]
BI
xxxx11
*7
Filter Sign Reset
[Circulating Water Exchange Sign Reset]
BV
xxxx12
*7
Prohibition On Off
BV
xxxx13
*4
Prohibition Mode
BV
xxxx14
*4
Prohibition Filter Sign Reset
[Prohibition Circulating Water Exchange Sign
Reset]
BV
xxxx15
*5, *7
Prohibition Set Temperature
BV
xxxx16
*4
M-NET Communication State
BI
xxxx20
System Forced Off
BV
xxxx21
999921
Air Direction Setup
MO
xxxx22
Air Direction State
MI
xxxx23
Set Temp Cool
AV
xxxx24
Set Temp Heat
AV
xxxx25
Set Temp Auto
AV
xxxx26
Set High Limit Setback Temp
AV
xxxx27
*6
Set Low Limit Setback Temp
AV
xxxx28
*6
Ventilation Mode Setup
MO
xxxx35
Ventilation Mode State
MI
xxxx36
Air To Water Mode Setup
MO
xxxx37
Air To Water Mode State
MI
xxxx38
Expansion Controller Communication State
BI
xx9981