- 15 -
3.5
Temperature setting objects
Select the temperature setting objects below according to the indoor unit group configuration in a given air conditioning
system.
Refer to section 8.4.5 “Configuring the Object settings” in BAC-HD150 Setting Tool Instruction Book for details.
: Selectable
: Not selectable
*1: When the operation mode is set to “AUTO (single set point)” on the remote controller, this setting will be used as the set
temperature for the AUTO mode on BAC-HD150.
When the operation mode is set to “AUTO (dual set points)” on the remote controller, [Set Temp Cool (AV_xxxx24)] and
[Set Temp Heat (AV_xxxx25)] will be used as the set temperatures for the AUTO mode on BAC-HD150.
*2: Not available depending on the type of units that are connected.
(1) Monitoring and setting temperatures from BMS
When setting the temperature settings for single set point indoor unit groups from BMS, use [Set Temp (AV_xxxx10)]. If BMS
uses the dual set point objects to send commands to single set point indoor unit groups, BAC-HD150 will send an error to
BMS.
Use [Set Temp (AV_xxxx10)] and [Set TempCool (AV_xxxx24)]-[Set Low Limit SetbackTemp (AV_xxxx28)] temperature setting
objects for dual set point indoor unit groups.
(2) When the BMS supports only the single set point function
Enable “Old Model Compatibility Mode” of the BAC-HD150 Setting Tool. BAC-HD150 will start up in the single set point mode.
Refer to section 8.2 “System Settings” in BAC-HD150 Setting Tool Instruction Book for details.
Control item
Object
type
Instance
number
Indoor unit group configuration
Notes
Single set point
group
Dual set point
group
Set Temp
AV
xxxx10
Set Temp Cool
AV
xxxx24
-
Set Temp Heat
AV
xxxx25
-
Set Temp Auto
AV
xxxx26
-
*1
Set High Limit
Setback Temp
AV
xxxx27
-
*2
Set Low Limit
Setback Temp
AV
xxxx28
-
*2
BAC-HD150
BMS
AV_xxxx24~
AV_xxxx28
AV_xxxx10
AV_xxxx10
AV_xxxx24~
AV_xxxx28
BACnet
®
M-NET
Request
Request
No Request
Request
Temperature setting
commands are sent to
indoor unit group 1.
Temperature setting
commands are sent to
indoor unit group 2.
An error is returned.
If BMS uses the dual set point
objects to send commands to
single set point indoor unit
groups, BAC-HD150 will return
an error to BMS.
Indoor unit group 1
Dual set point groups
Indoor unit group 2
Single set point groups