- 23 -

(2) Rotary switches

Rotary switches include SW606 and SW607.
SW606 and SW607 are used to operate BAC-HD150.
(Refer to section 6.7 Operation Functions for details.)

The arrow on the rotary switch indicates the current setting of the switch.
(The available setting range is 0 through F. The figure below shows representative values only.)
The figure below shows a rotary switch that is set to 0.

(3) Push switches

Push switches include SW605 and SW403.

(a) SW605

SW605 is used to use the display and operation functions.
(Refer to sections 6.6 Display Functions and 6.7 Operation Functions for details.)

(b) SW403

Press SW403 to restart BAC-HD150.

CAUTION:
Pressing SW403 will restart BAC-HD150. Use caution not to accidentally push this switch, for the 
Building Management System may falsely detect the communication with BAC-HD150 as an 
error.

0

4

8

C

WT05542X04.book  Page 23  Wednesday, July 3, 2013  12:13 PM

Summary of Contents for BAC-HD150

Page 1: ... Switch types 22 6 3 LED Types 24 6 4 Switch Setting Display 25 6 5 BAC HD150 Status and Mode Display 26 6 6 Display Functions 27 6 7 Operation Functions 28 6 8 Error Display 29 6 9 Recommended USB Drives 29 7 On site adjustment steps When BAC HD150 is connected to M NET 30 7 1 On site adjustment flowchart 30 7 2 Preparation for on site adjustment 31 7 3 Step 1 Initial setting for air conditioning...

Page 2: ...rly Contact your dealer for proper disposal procedures Do not attempt to modify or repair the BAC HD150 Modification or improper repair may result in electric shock or fire Consult your dealer when repairs are necessary Stop the operation immediately and notify your dealer if the BAC HD150 does not operate or when any abnormality is noticed Continuing the operation may result in damage to the BAC ...

Page 3: ...troduction Model Function Monitor Operation CITY MULTI S series Y series HP series R2 series WY series WR2 series HVRF series LOSSNAY OA Processing unit A control unit Mr Slim Requires an adapter AK control unit Mr Slim x K control unit Requires a converter Room air conditioner RAC Requires an adapter Air To Water Booster unit Air To Water HEX unit DOAS Dedicated Outside Air System ...

Page 4: ...wer Supply is recommended to be installed 5 Functions Due to continuing improvement specifications are subject to change without notice 6 Models in a group BAC HD150 monitors and controls indoor units for each group 1 To group multiple indoor units use the same models in a group 1 Group has two types a unit in a group or multiple units in a group 7 Request interval from BMS to BAC HD150 BMS Buildi...

Page 5: ...50 Setting Tool All indoor unit groups will be treated as single set point unit groups because the BAC HD150 will act as a single set point device Refer to section 8 2 System Settings in BAC HD150 Setting Tool Instruction Book for details d When using PAC YG50ECA Systems with connections to PAC YG50ECA and BAC HD150 do not support the dual set point function When using PAC YG50ECA enable Old Model...

Page 6: ...d to M NET M NET Mitsubishi Electric air conditioning control line 2 System configurations HUB BACnet BACnet M NET BAC HD150 BMS HUB Switching HUB Outdoor unit Outdoor unit Indoor unit Indoor unit ME remote controller ME remote controller LOSSNAY LOSSNAY LAN1 System controller M NET M NET HUB ...

Page 7: ...bjects in this manual and section 8 2 System Settings in BAC HD150 Setting Tool Instruction Book for details 㩷 㩷 㩷 㩷 㩷 㩷 BAC HD150 HUB 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 㩷 HUB HUB LAN1 LAN2 24VDC AG 150A PAC SC51KUA PAC YG50ECA BACnet BACnet M NET M NET M NET PAC YG50ECA M NET M NET M NET BMS Outdoor unit Outdoor unit Outdoor unit Outdoor unit Indoor unit Indoor unit ME remote controller ME remote controller ME re...

Page 8: ...tems of air conditioners BACnet IC 01 IC 02 IC 03 IC 04 IC 05 BAC HD150 M NET LAN1 Group No 01 Group No 03 Building Management System Air Conditioning system Unit address Group number M NET number 01 M NET number is fixed to 1 BAC HD150 is connected to M NET BACnet IC 01 IC 02 IC 03 IC 04 IC 05 BAC HD150 AG 150A M NET LAN1 LAN2 Group No 01 Group No 03 Building Management System Air Conditioning sy...

Page 9: ...Transmission medium 10BASE T 3 IP header Class C private address is recommended 1 Subnet Mask 255 255 255 0 1 Recommended value range 192 168 1 1 192 168 254 254 Do not use 192 168 0 0 and 192 168 255 255 as a device address 4 UDP header The default UDP port of unicast and broadcasting is set to 47808 0xBAC0 5 BVLL header BVLL BACnet Virtual Link Layer BVLC type 1 octet Fixed to 0x81 BVLL against ...

Page 10: ...lter Sign Circulating Water Exchange Sign M NET Communication State Expansion Controller Communication State 1 Binary Output 4 BO On Off Setup Binary Value 5 BV Filter Sign Reset Circulating Water Exchange Sign Reset Prohibition On Off Prohibition Mode Prohibition Filter Sign Reset Prohibition Circulating Water Exchange Sign Reset Prohibition Set Temperature System Forced Off 1 Calendar 6 Command ...

Page 11: ...State MI xxxx06 Cooling Heating Fan Auto Dry Setback 1 2 5 6 7 8 Fan Speed Setup MO xxxx07 Low High Mid 2 Mid 1 3 Fan Speed State MI xxxx08 Low High Mid 2 Mid 1 3 Room Temp Water Temp AI xxxx09 F C 10 Set Temp Set Water Temp AV xxxx10 F C 9 10 Filter Sign Circulating Water Exchange Sign BI xxxx11 OFF ON 10 Filter Sign Reset Circulating Water Exchange Sign Reset BV xxxx12 Reset Void 10 Prohibition ...

Page 12: ...g objects are used for different operation modes when using the dual set point function 8 Refer to Appendix outline of Auto dual set points and Setback modes for the difference between the operation mode AUTO dual set points and Setback 9 Temperature setting objects to be used for single set point indoor unit groups 10 Inside the brackets indicates control item for BU or AU group Refer to section ...

Page 13: ...ions Control item Object type Instance number Model group Note IC Group 3 LC Group BU AU Group On Off Setup BO xxxx01 On Off State BI xxxx02 Alarm Signal BI xxxx03 Error Code MI xxxx04 1 Operational Mode Setup MO xxxx05 Operational Mode State MI xxxx06 Fan Speed Setup MO xxxx07 Fan Speed State MI xxxx08 Room Temp Water Temp AI xxxx09 7 Set Temp Set Water Temp AV xxxx10 2 7 Filter Sign Circulating ...

Page 14: ...set point 19 30 C 17 28 C 19 28 C 19 30 C dual set points 19 35 C 4 5 28 C 19 35 C Mid temp model 14 30 C 17 28 C 17 28 C 14 30 C Mode Heating Heating ECO Hot Water Anti freez Cooling Booster unit BU 30 50 C 30 45 C 30 70 C 10 45 C Invalid HEX unit AU 30 45 C 30 45 C Invalid 10 45 C 10 30 C ...

Page 15: ...or to BMS Use Set Temp AV_xxxx10 and Set TempCool AV_xxxx24 Set Low Limit SetbackTemp AV_xxxx28 temperature setting objects for dual set point indoor unit groups 2 When the BMS supports only the single set point function Enable Old Model Compatibility Mode of the BAC HD150 Setting Tool BAC HD150 will start up in the single set point mode Refer to section 8 2 System Settings in BAC HD150 Setting To...

Page 16: ... Service 9 Subscribe COV Property Service 2 File Access Services 1 Atomic Read File Service 2 Atomic Write File Service 3 Object Access Services 1 Add List Element Service 2 Remove List Element Service 3 Create Object Service 4 Delete Object Service 5 Read Property Service 6 Read Property Conditional Service 7 Read Property Multiple Service 8 Read Range Service 9 Write Property Service 10 Write Pr...

Page 17: ...st 6 Security Services 1 Authenticate Service 2 Request Key Service 7 Unconfirmed Services 1 I Am 2 I Have 3 Unconfirmed COV Notification Service 4 Unconfirmed Event Notification Service 5 Unconfirmed Private Transfer Service 6 Unconfirmed Text Message Service 7 Time Synchronization Service 8 UTC Time Synchronization Service 9 Who Has 10 Who Is ...

Page 18: ...Class Confirmed COV Notification INIT EXEC Confirmed Event Notification INIT EXEC Get Event Information INIT EXEC Subscribe COV INIT EXEC Add List Element INIT EXEC Remove List Element INIT EXEC Read Property INIT EXEC Read Property Multiple INIT EXEC Write Property INIT EXEC Write Property Multiple INIT EXEC Device Communication Control INIT EXEC I Am INIT EXEC I Have INIT EXEC Unconfirmed COV No...

Page 19: ...p MO_xxxx07 Fan Speed State MI_xxxx08 Room Temp Water Temp AI_xxxx09 1 Set Temp Set Water Temp AV_xxxx10 1 Filter Sign Circulating Water Exchange Sign BI_xxxx11 1 Filter Sign Reset Circulating Water Exchange Sign Reset BV_xxxx12 1 Prohibition On Off BV_xxxx13 Prohibition Mode BV_xxxx14 Prohibition Filter Sign Reset Prohibition Circulating Water Exchange Sign Reset BV_xxxx15 1 Prohibition Set Tempe...

Page 20: ...ror Code 1 1 Normal 8000 or all the codes except No 2 No 9 2 2 Other errors 0000 0999 6000 6499 6750 6779 3 3 Refrigeration system fault 1000 1999 4 4 Water system error 2000 2999 5 5 Air system error 3000 3999 6 6 Electronic system error 4000 4999 7 7 Sensor fault 5000 5999 8 8 Communication error 6500 6749 6780 6999 9 9 System error 7000 7999 ...

Page 21: ...em to which Expansion Controllers PAC YG50ECA are connected be sure to restart the BAC HD150 to reflect the changes 5 3 Mode of BAC HD150 BAC HD150 has Online mode and Offline mode Online mode is an operation mode to perform BACnet communication 2 and M NET Expansion Controller communication Offline mode is a maintenance mode in which BACnet communication is not performed It is the mode in which t...

Page 22: ...ons for details b SW602 SW602 is used to operate BAC HD150 Refer to section 6 7 Operation Functions for details c SW901 Set SW901 to 00000100 0 OFF 1 ON Set No 6 to ON d SW902 Leave all switches to OFF 6 Switches and LED display 7segment LED SW604 SW603 SW602 SW607 SW601 SW403 SW901 SW902 Error LED LED902 SW605 SW606 Switch Board Main Board TB1 TB3 M NET Board USB connector CN60 M NET LED LED901 L...

Page 23: ...tive values only The figure below shows a rotary switch that is set to 0 3 Push switches Push switches include SW605 and SW403 a SW605 SW605 is used to use the display and operation functions Refer to sections 6 6 Display Functions and 6 7 Operation Functions for details b SW403 Press SW403 to restart BAC HD150 CAUTION Pressing SW403 will restart BAC HD150 Use caution not to accidentally push this...

Page 24: ...unctions for details Shown below are the codes that appear in the 7segment LED that correspond to alphabetic letters LED name Display items Display contents M NET Device power supply status and M NET communication status Lit Powered Unlit Not powered Blink M NET transmission in progress LAN1 LAN 1 BACnet communication status Lit Linking Unlit Not linked Blink Transmitting LAN2 LAN 2 Expansion Cont...

Page 25: ...t corresponds to b in the figure above C will appear in the position that corresponds to a in the figure above If any one of the switches on both SW601 and SW602 are set to ON 1 Er11 will appear in the 7segment LED 1 Any combinations of switch settings other than the combination in which all switches are set to OFF The following table shows the switch settings and the corresponding data in the hex...

Page 26: ...play the summarized status of all PAC YG50ECA controllers 2 Includes communication error LD1 CPU status Lit Normal Unlit Error LD2 Expansion Controller communication status Lit Error Unlit Normal LD3 BACnet communication status Lit Error Unlit Normal LD4 Error status Lit At least one air conditioning unit is in error 2 Unlit All units are normal LD5 M NET Expansion Controller startup status 1 Unli...

Page 27: ...g displayed The IP address 192 168 1 254 will appear as follows in the 7segment LED No SW601 0 OFF 1 ON Display item 7segment LED display 1 2 3 4 5 6 7 8 0 0 0 0 0 0 0 0 0 Not selected 1 0 0 0 0 0 0 0 1 BACnet Communication Service status 0100 Enable 0101 Disable 0102 Disable Initiation 2 0 0 0 0 0 0 1 0 Not used 3 0 0 0 0 0 0 1 1 Not used 4 0 0 0 0 0 1 0 0 Not used 5 0 0 0 0 0 1 0 1 Not used 6 0 ...

Page 28: ... 0 0 Not selected 1 0 0 0 1 For maintenance use 2 0 0 1 0 For maintenance use 3 0 0 1 1 Not used 4 0 1 0 0 For maintenance use 5 0 1 0 1 For maintenance use 6 0 1 1 0 Not used 7 0 1 1 1 Not used 8 1 0 0 0 For maintenance use 9 1 0 0 1 Not used 10 1 0 1 0 Not used 11 1 0 1 1 Not used 12 1 1 0 0 Not used 13 1 1 0 1 Not used 14 1 1 1 0 SW606 F SW607 F Batch operation 15 1 1 1 1 SW606 F SW607 F Batch ...

Page 29: ...Model name SDCZ6 4096RB Memory size 4GB Manufacturer Kingston Model name DT400 2GBFE Memory size 2GB Manufacturer A DATA Model name C702 Memory size 2GB 4GB There may be some USB drives that are not compatible with BAC HD150 CAUTION When executing a batch operation the ON signal will be sent to all groups of units The operation status information about each group before the command is executed wil...

Page 30: ... with the Setting Tool for BAC HD150 system setting and group setting for air conditioning system Step 2 Test run of air conditioning system Check that air conditioning units and controllers are system configured correctly and operate properly Refer to the Installation Manual that came with each device for how to perform test run Step 3 Initial settings for BACnet related items Make the setting fo...

Page 31: ...ks and Installation Manuals Miscellaneous BACnet device list Documents related to notification items destinations and methods Tools and parts Computer For Setting Tool USB memory For setting data backup Installation CD for the Setting Tool Setup disk HUB For connection to Setting Tool Two LAN cables category 5 or above straight cable For connection to Setting Tool General tools such as a driver Te...

Page 32: ...er to the Instruction Book that came with Setting Tool for setting method No Main tab Sub tab Setting item 1 System Settings Basic System All setting items 2 M NET All setting items 3 Expansion Controller No settings required 4 Group Settings Group All setting items 5 LOSSNAY All setting items CAUTION If IP address of BAC HD150 overlaps any of the addresses that are assigned to other devices commu...

Page 33: ...he setting data made in Step 1 such as air conditioning system group is automatically sent from BAC HD150 to air conditioning system It may take about 5 minutes for the setting 4 Test run using system controller or remote controller Perform test run using system controller or remote controller to check operation status of each unit Refer to the Installation Manual that came with air conditioning u...

Page 34: ...ng Tool for setting method No Main tab Sub tab Setting item 1 BACnet Settings BACnet All setting items 2 Network and Device All setting items 3 COV Notification All setting items 4 Event Notification All setting items 5 Object All setting items 6 Other All setting items HUB HUB BACnet M NET M NET M NET BAC HD150 Step 3 Outdoor unit Outdoor unit Indoor unit Indoor unit ME remote controller ME remot...

Page 35: ... HD150 to BACnet 3 Restarting the BAC HD150 Restart BAC HD150 then it becomes Online mode 4 Test run items and method Refer to Appendix On site adjustment sheet for BAC HD150 proposal for the test run items and method HUB HUB BACnet Step 4 㩷 HUB LAN2 LAN1 M NET M NET M NET Outdoor unit Outdoor unit Indoor unit Indoor unit ME remote controller ME remote controller System controller Setting Tool LOS...

Page 36: ...ustment can be identified efficiently It is recommended to follow the steps below 8 On site adjustment steps When BAC HD150 is connected to PAC YG50ECA Step 1 Initial settings for the BAC HD150 system and BACnet related items Make the setting for the BAC HD150 system and BACnet related items by using Setting Tool Refer to the Instruction Book that came with Setting Tool for BAC HD150 system settin...

Page 37: ...tion Manuals Miscellaneous BACnet device list Documents related to notification items destinations and methods Tools and parts Computer For Setting Tool USB memory For setting data backup Installation CD for the Setting Tool Setup disk HUB For connection to Setting Tool Two LAN cables category 5 or above straight cable For connection to Setting Tool General tools such as a driver Tester Use to che...

Page 38: ...from BACnet 3 Connecting the Setting Tool Use additional HUB2 to connect BAC HD150 and Setting Tool Disconnect the cable that is connected to LAN2 port of BAC HD150 from HUB1 and connect it to the additional HUB2 㩷 㩷 㩷 㩷 㩷 BAC HD150 HUB 㩷 㩷 㩷 㩷 㩷 LAN PAC YG50ECA M NET PAC YG50ECA M NET 24VDC PAC SC51KUA HUB HUB1 LAN1 LAN2 AG 150A PAC YG50ECA BACnet BACnet M NET M NET M NET BMS Outdoor unit Outdoor...

Page 39: ...uired 3 Expansion Controller Access Point Settings 4 Group Settings Group No settings required 5 LOSSNAY No settings required 6 BACnet Settings BACnet All setting items 7 Network and Device All setting items 8 COV Notification All setting items 9 Event Notification All setting items 10 Object All setting items 11 Other All setting items CAUTION If IP address of BAC HD150 overlaps any of the addres...

Page 40: ...at the Expansion Controller Settings match the settings that were made from AG 150A Refer to section 8 2 3 1 Acquiring the settings information for the Expansion Controller settings in the BAC HD150 Setting Tool Instruction Book for how to acquire the settings information of PAC YG50ECA Restart BAC HD150 then it becomes Online mode 5 Disconnecting the Setting Tool and connecting BAC HD150 to HUB o...

Page 41: ...4 Auto 05 Dry 4 06 Setback Change operation mode of the specific group from BMS After doing so check that the operation mode of the group renews the mode using system controller or remote controller Operational Mode State MI_xxxx06 01 Cooling 02 Heating 03 Fan 04 Auto 05 Dry 4 06 Setback Change operation mode of the specific group using system controller or remote controller After doing so check t...

Page 42: ...ct M NET transmission line to BAC HD150 or PAC YG50ECA After doing so check that the M NET communication status of all groups turns to Normal INACTIVE on BMS System Forced Off BV_xxxx21 BV_999921 INACTIVE Reset ACTIVE Execute Perform a forced stop of the system of the specific group from BMS After doing so check that the air conditioner stops on BMS Air Direction Setup MO_xxxx22 01 Horizontal 02 D...

Page 43: ...er limit temperature in setback mode of the group renews the temperature using system controller or remote controller Change the set lower limit temperature in setback mode of the specific group using system controller or remote controller After doing so check that the set lower limit temperature in setback mode of the group renews the temperature on BMS Ventilation Mode Setup MO_xxxx35 01 Heat ex...

Page 44: ...etween the highest and the lowest is large and both heating and cooling modes are used within the same day Setback mode Room temperature is controlled to stay within the set temperature range that is specified for the Setback mode By leaving sufficient temperature differential between the set temperature for cooling upper limit and heating lower limit it is possible to keep the room temperature wi...

Page 45: ... radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna I...

Page 46: ......

Page 47: ......

Page 48: ...Recycled Paper Please be sure to put the contact address telephone number on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC Restriction of Hazardo...