- 29 -
(1) Batch operation (Sending the “ON” signal to all groups of units)
Set SW602 to “1110,” SW606 to “F,” and SW607 to “F,” and then press and hold SW605 for two seconds or longer to send the
“ON” signal to all groups of units.
After the “ON” signal has been sent, “End” will appear in the 7segment LED display.
(2) Batch operation (Sending the “OFF” signal to all groups of units)
Set SW602 to “1111,” SW606 to “F,” and SW607 to “F,” and then press and hold SW605 for two seconds or longer to send the
“OFF” signal to all groups of units.
After the “OFF” signal has been sent, “End” will appear in the 7segment LED display.
6.8
Error Display
An error code will be displayed in the 7segment LED if an error occurs upon execution of display or operation functions.
6.9
Recommended USB Drives
The following types of USB drives are recommended for use with BAC-HD150.
• Manufacturer : Sandisk
Model name : SDCZ6-2048-J65RB
Memory size : 2GB
• Manufacturer : Sandisk
Model name : SDCZ6-4096RB
Memory size : 4GB
• Manufacturer : Kingston
Model name : DT400/2GBFE
Memory size : 2GB
• Manufacturer : A-DATA
Model name : C702
Memory size : 2GB/4GB
There may be some USB drives that are not compatible with BAC-HD150.
CAUTION:
When executing a batch operation, the “ON” signal will be sent to all groups of units. The
operation status information about each group before the command is executed will not be
stored.
To restore the original operation status before the batch operation command was sent, each
group needs to be set to ON or OFF individually.
CAUTION:
When executing a batch operation, the “OFF” signal will be sent to all groups of units. The
operation status information about each group before the command is executed will not be
stored.
To restore the original operation status before the batch operation command was sent, each
group needs to be set to ON or OFF individually.
No.
Error code
Cause of error
1
Er11
One or more switches on both SW601 and SW602 are set to ON.
2
Er12
One or more of the unavailable switches of SW601 or SW602 are set to ON.
3
Er13
Either SW606 or SW607 is set incorrectly.
WT05542X04.book Page 29 Wednesday, July 3, 2013 12:13 PM