MIV V5 Heat Recovery DC Inverter R410A
DM14-01.01.18en
Troubleshooting
166
4.6 E8: Outdoor unit address is wrong
The error only display on faulty slave unit, all the ODU will be standby.
4.7 XE9: Driver model is mismatching (When X is 1, it means A system; 2 means B system)
E8: Outdoor unit address is wrong
The ODU's address is more than 3 or
be set repeatedly
The addresses should be set less
than 3 and differently
Outdoor main PCB is
damaged
Replace the outdoor
main PCB
No
Yes
The communication wires H1, H2 and
E are short circuit or disconnected. If
the resistance between H1, H2andE is
zero or very small, the reason is short
circuit; If using the multimeter testing
the communication wires don’t have
belling sound, the reason is
disconnected.
Replace or reconnect the
communication wires
Yes
No
Yes
E9: Driver model is mismatching
Power on the outdoor unit immediately
after it is power off
If the outdoor unit is power off, the unit
should be power on after the digital
tube is power off
Outdoor main PCB is damaged
Replace the outdoor main PCB
No
Yes
Yes