MIV V5 Heat Recovery DC Inverter R410A
DM14-01.01.18en
Troubleshooting
154
When the outdoor unit is in standby, the first two numbers on LED digital tube will display the address of the outdoor unit, and the
last two numbers display the indoor unit’s quantity which can communicate with outdoor unit. When the outdoor unit is operating,
it will display the rotation frequency of the compressor.
1. Outdoor unit capacity setting: 0: 8HP; 1: 10HP; 2: 12HP; 3: 14HP; 4: 16HP
2. Running mode: 0—closed; 2—cooling mode; 3—heating mode; 4—forced cooling mode.
3. Fan speed: 0—closed; 1~15—fan speed increase in sequence.
4. State of the outdoor heat exchanger: 0-close/condenser; 1-All evaporator; 2-Left evaporator/right condenser; 3-Left
evaporator/close.
5. Silent mode: 0—nighttime silent mode; 1—silent mode; 2—super silent mode; 3—no silent mode.
6. Static pressure mode: 0—no static pressure; 1—low static pressure; 2—medium static pressure; 3—high static pressure.
2.2.2 Dial switch setting
S1: Starting time setting
Starting time is 10 minutes
Starting time is 12 minutes (default)
S2: Night silent time setting
Night silent time is 6h/10h (default)
Night silent time is 6h/12h
Night silent time is 8h/10h
Night silent time is 8h/12h
S3: Silent mode selection
Night silent mode (default)
Silent mode
Super silent mode.
None silent mode.
S4: Static pressure mode selection
None static pressure(default)
Low static pressure mode (reserved, can be customized)
Medium static pressure mode (reserved, can be customized)
High static pressure mode (reserved, can be customized)
S1
S1
S2
S2
S2
S2
S3
S3
S3
S3
S4
S4
S4
S4