DM14-01.01.18en
MIV V5 Heat Recovery DC Inverter R410A
Installation Procedure
128
12.5 Dial switch setting
S1: Starting time setting
Starting time is 10 minutes
Starting time is 12 minutes (default)
S2: Night silent time setting
Night silent time is 6h/10h (default)
Night silent time is 6h/12h
Night silent time is 8h/10h
Night silent time is 8h/12h
S3: Silent mode selection
Night silent mode (default)
Silent mode
Super silent mode.
None silent mode.
S4: Static pressure mode selection
None static pressure(default)
Low static pressure mode (reserved, can be customized)
Medium static pressure mode (reserved, can be customized)
High static pressure mode (reserved, can be customized)
ENC3+S12: Indoor unit quantity setting
The quantity of indoor unit is 0-15
The quantity of indoor unit is 16-31
The quantity of indoor unit is 32-47
The quantity of indoor unit is 48-63
ENC1: Outdoor unit address setting
Only 0, 1, 2, 3 are available.
0 is for main unit; 1, 2, 3 are for slave units
ENC2: Outdoor unit capacity setting