![Midea MVUR252B-VA3 Service Manual Download Page 155](http://html1.mh-extra.com/html/midea/mvur252b-va3/mvur252b-va3_service-manual_1791261155.webp)
DM14-01.01.18en
MIV V5 Heat Recovery DC Inverter R410A
153
Troubleshooting
2.2.1 Spot check content instructions
No.
Normal
display
Content (present frequency)
Note
1
0 - -
Outdoor unit address
0, 1, 2, 3
2
1 - -
Outdoor unit capacity setting
Refer to note 1
3
2 - -
Outdoor unit quantity
Available for main outdoor unit
4
3 - -
Running mode
Refer to note 2
5
4 - -
Total capacity of outdoor units
Capacity requirement
6
5 - -
Cooling capacity
Slave unit only display capacity of main mode
7
6 - -
Heating capacity
Slave unit only display capacity of main mode
8
7 - -
Ambient temperature revision of cooling capacity
Capacity requirements
9
8 - -
Ambient temperature revision of heating capacity
Capacity requirements
10
9 - -
Actual running capacity of this outdoor unit
Capacity requirement
11
10 - -
Fan A speed
Refer to note 3
12
11 - -
Fan B speed
Refer to note 3
13
12 - -
T2 average temperature
Actual value=display value
14
13 - -
T2B average temperature
Actual value=display value
15
14 - -
T3 left pipe temperature
Actual value=display value
16
15 - -
T5 right pipe temperature
Actual value=display value
17
16 - -
T4 ambient temperature
Actual value=display value
18
17 - -
Discharge temperature of inverter compressor A
Actual value=display value
19
18 - -
Discharge temperature of inverter compressor B
Actual value=display value
20
19 - -
Inverter module temperature
Actual value=display value
21
20 - -
Discharge pressure corresponding to the saturation
temperature
Actual value=display value-30
22
21 - -
The minimum overheating temperature of discharge
Actual value=display value
23
22 - -
Current of inverter compressor A
Actual value=display value
24
23 - -
Current of inverter compressor B
Actual value=display value
25
24 - -
State of the outdoor heat exchanger
Refer to note 4
26
25 - -
EXVA opening degree
Pulsed value=display value×8
27
26 - -
EXVB opening degree
Pulsed value=display value×8
28
27 - -
Discharge pressure value
Actual value=display value×0.1MPa
29
28 - -
Indoor units quantity
Actual value=display value
30
29 - -
Cooling indoor units quantity
Cooling indoor units quantity
31
30 - -
Heating indoor units quantity
Cooling indoor units quantity
32
31 - -
Reserved
/
33
32 - -
Silent mode
Refer to note 5
34
33 - -
Static pressure mode
Refer to note 6
35
34 - -
DC voltage A
Actual value=display value×10
36
35 - -
DC voltage B
Actual value=display value×10
37
36 - -
Reserved
/
38
37 - -
Reserved
/
39
38 - -
The last error or protection code
Display 000 if it has no error or protection
40
39 - -
- -
Over
Note: