MIV V5 Heat Recovery DC Inverter R410A
Installation Procedure
104
3. Master and slave unit setting
When the quantity of outdoor unit is more than two in one system, the outdoor unit should be placed form large
capacity unit to small capacity unit. The largest capacity unit must be placed at the first branch site, and be set
as master unit, while the other are set as slave units.
Take 38HP (composed by 10HP, 12HP and 16HP) as an example:
1) Place the 16HP at a side of the first branch site.
2) Place the unit from the large capacity to small (See the detail placement illustration)
3) Set 16HP as the master unit, while the 12HP and the 10HP as slave units.
The 1st branch joint
Outdoor unit
16HP
12HP
10HP
(38HP)
Indoor unit A
MS
Indoor unit B Indoor unit C
MS
MS