MIV V5 Heat Recovery DC Inverter R410A
DM14-01.01.18en
131
Installation
Procedure
Calculate the critical thickness through following steps, and take necessary actions.
1. Calculate the refrigerant charge A
2. Total refrigerant charge = delivered refrigerant charge (nameplate) + supplemental refrigerant charge
3. Calculate the indoor volume (B) (as the minimum volume)
4. Calculate the refrigerant thickness.
A/B
≤
critical thickness 0.3kg/m3
Countermeasure to over-high refrigerant thickness
1. Install mechanical ventilator to reduce the refrigerant thickness
under critical level. (Ventilate regularly)
2. Install leakage detector alarming device related to mechanical
ventilator if you cannot regularly ventilate.
Indoor unit
OA
air-vent
Leakage detector alarming device
related to mechanical ventilator