DM14-01.01.18en
MIV V5 Heat Recovery DC Inverter R410A
155
Troubleshooting
Dial switch setting
ENC3+S12: Indoor unit quantity setting
The quantity of indoor unit is 0-15
The quantity of indoor unit is 16-31
The quantity of indoor unit is 32-47
The quantity of indoor unit is 48-63
ENC1: Outdoor unit address setting
Only 0, 1, 2, 3 are available.
0 is for main unit; 1, 2, 3 are for slave units
ENC2: Outdoor unit capacity setting
Only 0, 1, 2, 3, 4 are available.
0: 8HP; 1: 10HP; 2: 12HP; 3: 14HP; 4: 16HP
ENC4: Network address setting
Only 0, 1, 2, 3, 4, 5, 6, 7 are available.
ENC3
S12
ENC3
S12
ENC3
S12
ENC3
S12