MIV V5 Heat Recovery DC Inverter R410A
Installation Procedure
120
10. Vacuum
Use the vacuum pump which vacuum level lower than -0.1MPa and the air discharge capacity above
40L/min.
The outdoor unit is not necessary to vacuum, don’t open the outdoor unit gas and liquid pipe shut-off valves.
Make sure the vacuum pump could result as -0.1MPa or below after 2 hours or above operation. If the pump
operated 3 hours or above could not achieve to -0.1MPa or below, please check whether water mix or gas
leak inside of the pipe.
Pressure gauge with the switch is installed between vacuum pump and system pipes.