DM14-01.01.18en
MIV V5 Heat Recovery DC Inverter R410A
Installation Procedure
108
Unit: mm
Example A
A A
≥
300
B B
≥
250
C C
≤
3000
D 725
≤
D
≤
760
θ
θ≤
15
°
Outdoor fan performance
The default static pressure of outdoor unit is 0 Pa, and 20Pa can be achieved when the steel mesh is removed.
8/10HP 12HP
14/16HP
Remove the two
iron filters firstly
12 ST3.9 self-threading screws
28-9/16(725)
12-
Φ
1/8(3.2)
3
9
3
5
67
16-3/16
(411)
16-3/16
(411)
8-3/8
(213)
16-3/16
(411)
16-3/16
(411)
8-3/8
(213)
49-7/32(1250)
3/8(10)
3/
8(
10)
Static pressure Pa(in.WG)
Air volume m
3
/h(CFM)
9500(5590)
10000(5880)
10500(6180)
11000(6470)
11500(6760)
12000(7060)
12500(7350)
0(0)
5(0.02) 10(0.04) 15(0.06) 20(0.08) 25(0.1)
Static pressure Pa(in.WG)
Air volume m
3
/h(CFM)
0(0)
5(0.02) 10(0.04) 15(0.06) 20(0.08) 25(0.1)
10500(6180)
11000(6470)
11500(6760)
12000(7060)
12500(7350)
13000(7650)
13500(7940)
Static pressure Pa(in.WG)
Air volume m
3
/h(CFM)
0(0)
5(0.02) 10(0.04) 15(0.06) 20(0.08) 25(0.1)
12500(7350)
13000(7650)
13500(7940)
14000(8240)
14500(8530)
15000(8830)
15500(9120)
Example B
A A
≥
300
B B
≥
250
C C
≤
3000
θ
θ≤
15
°
Note:
Before install the ventilation assembly, please remove the steel
meshes firstly, otherwise, they would decrease the air supply
volume.
1. Increase shutters would decreases the air supply volume, as
well as cooling (heating) capacity and energy efficiency would be
decreased, the larger angle of the shutter, the more effect to the
unit. So we don’t recommend applying shutter, if necessary to
apply shutter, please ensuring the angle should not over than 15°.
2. The bending place at ventilated duct should be not more than
1(show in above figure), otherwise, operation malfunction would be
caused.
3. Install the flexible connector between the unit and the air
deflector pipe to avoid vibration noise.