MIV V5 Heat Recovery DC Inverter R410A
DM14-01.01.18en
115
Installation
Procedure
6.4 Piping connection between outdoor units
All connection pipes between outdoor units should be horizontally, it is not allowed the concave at junction site.
The height of each connection pipe between outdoor units is not allowed to over the height of refrigerant outlet
pipe.
.
6.5 Branch pipe installation
The branching pipe must be installed horizontally and error angle of it should not be larger than 10°. Otherwise,
refrigerant assignment will be uneven and malfunction will be caused.
For avoiding oil accumulate at the outdoor unit, please install the branching pipes properly.
√
Correct way
Correct way
× Wrong way
× Wrong way
10°
10°
A
Correct
Wrong
U-shaped branching pipe
Horizontal surface
A direction view