MIV V5 Heat Recovery DC Inverter R410A
Installation Procedure
106
unit to facilitate heat dissipation. See the figure below. The height of the air director is HD (namely H-h).
Please make the air director on site.
Unit: in.(mm)
If miscellaneous articles are piled around the outdoor unit, such articles must be 800mm below the top of the
outdoor unit. The articles must be 800mm below the top of the outdoor unit. Otherwise, a mechanic exhaust
device must be added.
Unit: in.(mm)
Set the snow-proof facility
In snowy areas, facilities should be installed to prevent snow. (See the figure below) (Defective facilities may
cause malfunction.) Please lift the bracket higher and install snow shield at the air inlet
and air outlet.
Snow shield for air outlet
Snow shield for air inlet
Snow shield for air inlet