MS Unit Installation
6.1 Power supply specifications
The power supply cable specifications are as follows. In case power capacity is too low may result in
over-heating of piping that would be burned out the unit.
Item
Model
Power supply
(V/Ph/Hz)
Power switch
Power supply cable
Signal wire
Capacity
(A)
Safety
fuse (A)
Power wire
Ground wire
MS02/N1-C 220-240/1/50~60 5
5
2×14AWG 1×14AWG
3-core shielded wire
20AWG
MS04/N1-C 220-240/1/50~60
5 5
2×14AWG
1×14AWG
3-core shielded wire
20AWG
MS06/N1-C 220-240/1/50~60
5 5
2×14AWG
1×14AWG
3-core shielded wire
20AWG
MS02E/N1-C 220-240/1/50~60
5 5
2×14AWG
1×14AWG
3-core shielded wire
20AWG
MS04E/N1-C 220-240/1/50~60
5 5
2×14AWG
1×14AWG
3-core shielded wire
20AWG
6.2 Wiring for the MS power wire and signal wire
1. Please use dedicated power supply different from the outdoor unit for the MS power.
2. The power, electrical leakage protectors and operation switches for each indoor unit connected to the
same outdoor unit and the MS should be in common use.
3. The MS power wire should be connected to the terminals with the label “L, N”, and the MS signal wire
should be connected to the terminals with the label “P, Q, E” and correspond to the “P, Q, E” wiring
terminals for the outdoor and indoor units, which cannot be wrong connected. Please refer to the following
figures.
Wiring diagrams
MS02/N1-C
M-O
M-I
TRANS
P Q E
P Q E
P Q E
T2C1 T2C2
Y/G
CN13
POWER IN
TO INDOOR2 TO INDOOR1
TO OUTDOOR