5-24
MICRONIX USA, LLC
www.micronixusa.com
Rev: 3.02
Deceleration
During Motion
Real-time
Program
Global
Set
Read
Set
Read
Set
Read
Set
Read
Command
Description:
This command is used to set the desired deceleration for the
specified axis, distinct from the acceleration [ACC]. The
deceleration value must be less than the maximum acceleration
value [AMX] for the command to be accepted.
Returns:
A read operation returns the deceleration value in mm/s
2
for the
specified axis.
Syntax:
nDECx
–
Standard syntax
nDEC?
–
Read deceleration value
0DECn
–
All axes set deceleration value
Error [#]:
DEC?
–
Read operation with missing axis number [27]
nDEC
–
Missing deceleration parameter [28]
Parameter
Description:
n[int]
–
Axis number
x[float]
–
Deceleration
?
–
Read deceleration value
Parameter
Range:
n
–
0 to 99
x
–
000.001 to AMX (500.000 mm/s
2
) [degrees/s
2
]
Related Commands: ACC, AMX, VEL
Example:
2DEC1.25
|
Axis 2, Set deceleration to 1.25 mm/s
2
[degrees/s
2
]
-
7DEC?
|
Axis 7, Read deceleration value
Summary of Contents for MMC-200 Series