Calculate the critical thickness through following steps, and take necessary actions.
1)
Calculate the refrigerant charge volume A, A= factory charge additional charge
volume
2)
Calculate the indoor area volume (B) (as the minimum volume)
3)
Calculate the refrigerant thickness, A/B ≤ critical thickness 0.3kg/m
3.
In d o o r U n it
Full of le a king re frige ra nt
All the re frige ra nt ha s le a ke d