MegaLife
ARV OUTDOOR UNIT
–
ARV 6 ALL DC INVERTER T1 50&60HZ Service Manual
136
2. The connection between PCB and
step motor failure.
A8
Indoor unit ERRPROM module failure
1. Indoor unit PCB is broken
2. Error module is broken
AC
More than 2 indoor units
’ central control
system address repeated
The central control address setting
incorrect
AE
Operation mode conflict
The operation mode setting incorrect
AH
Two or more indoor unit refrigerant system
address repeated
System address setting incorrect
AJ
Indoor unit total capacity exceeded
Stop some indoor units
AF
The EXV leakage
1. EXV is blocked
2. Evaporator inlet sensor failure.
3.
Indoor unit’s temp. sensor failure
A0
The EXV open failure
2. ODU Error code table (No.65)
2.1 Communication failure (4)
Code
Definition
Possible reason for error code
J1
Communication failure between
outdoor units
1. The communication wire between
outdoor units is disconnect, short circuit or
incorrect
2. Outdoor unit
’s main PCB failure
3.
Outdoor unit’s main power failed
J2
Communication failure between
1. The communication wire between
Summary of Contents for ARV Series
Page 71: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 71...
Page 88: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 88...
Page 114: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 114...
Page 118: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 118...
Page 131: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 131...
Page 150: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ 150 Symbol Description...
Page 151: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ 151...
Page 172: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 172...