whole system until.
1.5 ODU static pressure control
If the installation space the same as
right diagram
1. Air exhausting device is necessary to be
added to improve the ventilation
2.
Outdoor unit’s static pressure should be set
to
20 or 50 or 80Pa
according the air
exchausting device
Before power on, outdoor unit’s static pressure can be set to 20/50/80Pa
according to project demand
(Change according “
Part 3 - 4.1 Functions set by
switch
”
SW5
)
1.6 Clean (Auto dust removal)
Outdoor fan motor run as opposite direction for a period of time to blow away the dust
(Choose the function according “
Part 3 – 4.2.4 [C] Function Setting
“-
【
C……2
】
)
1.7 Blow off Snow (Auto snow-blowing)
The fan motor will run for a period of time to blow away the snow
(Choose the function
according “
Part 3 – 4.2.4 [C] Function Setting
“ -
【
C…..4
】
)
D
C
C
< 1000 mm
D
A ir e xh a u stin g d e vic e
50 Pa
1
SW5
O N
ON ON
5 6
2
ODU sta tic pressure
3 4 5 6 7 8
80 Pa
1
SW5
O N
OFF ON
5 6
2
ODU sta tic pressure
3 4 5 6 7 8
20 Pa
3 4 5 6 7 8
1
SW5
O N
ON OFF
5 6
2
ODU sta tic pressure
Summary of Contents for ARV Series
Page 71: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 71...
Page 88: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 88...
Page 114: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 114...
Page 118: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 118...
Page 131: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 131...
Page 150: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ 150 Symbol Description...
Page 151: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ 151...
Page 172: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 172...