ARV 6 ALL DC INVERTER T1 50&60HZ Service Manual
115
6.3 Parameter setting by XK-02A
6.3.1 Enter the setting interface
①
Press [
Filter Net Button
] for
5 seconds,
group number
“01”
of wired controller will be
displayed in temperature zone of LCD screen and
“0101”
will be displayed in timing setting
zone of LCD screen.
②
“
0101
” means this indoor unit ID a
ddress is No. 1
③
Press [
+/- Button of Time
],
“0201”, “0301”, “0401” “0510”
will be displayed
successively. Check
“
6.1 Parameter Setting Items
” for number of parameters and
corresponding meaning.
6.3.2 Parameter Setting
After press [
Filter Net Button
] for
5 seconds
, then
1. Press [
Time +/- button
] to change number of parameters (
1~15
),
“
01
01”
~
“
15
01”
2. Press [
Mode Button
] once,
“01
01
”
,
01
will flash
3. Press [
Temp +/- button
] to change the value, for example
“01
05
”
Summary of Contents for ARV Series
Page 71: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 71...
Page 88: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 88...
Page 114: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 114...
Page 118: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 118...
Page 131: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 131...
Page 150: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ 150 Symbol Description...
Page 151: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ 151...
Page 172: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 172...