ARV OUTDOOR UNIT
–
ARV 6 ALL DC INVERTER T1 50&60HZ Service Manual
140
2.5 Temperature abnormal (3)
Code
Definition
Possible reason for error code
FH
Discharge temperature too low
Compressor failure
E3
【
T
da
】
1# Compressor discharge
temperature too high
1.System lack of refrigerant
2.DC inverter Compressor failure
3.Compressor air return filter block
4.EXV block
5.Gas stop valve was closed
6.Liquid stop valve was closed
7.dischargr sensor failure
8.Outdoor unit PCB failure
E4
【
T
db
】
2# Compressor discharge
temperature too high
2.6 1# Comp. and drive failure (11)
Code
Definition
Possible reason for error code
31
Drive Module IPM protection (F0)
1. Low supply voltage, excessive current
2. Supply voltage exceed limit
3. Outdoor fan stop or low speed
4. Drive module temp. too high
32
Drive Module hardware protection
33
Drive Module software protection
34
Drive module unconnected
1.The connect of driving module and DC
inverter compressor incorrect
2.Driving module failure
3.Compressor failure
Summary of Contents for ARV Series
Page 71: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 71...
Page 88: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 88...
Page 114: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 114...
Page 118: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 118...
Page 131: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 131...
Page 150: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ 150 Symbol Description...
Page 151: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ 151...
Page 172: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 172...