49
Drive module IPM alarm
2.10
Others failure (10)
Code
Definition
Possible reason for error code
H1
(B1)
【
HP1
】
High
pressure
switch failure
1. High pressure exceed high pressure switch limit.
2. High pressure switch failure
3. High pressure sensor failure
4. Instantaneous power-off
5. Stop valve closed
6. Outdoor unit fan stop
7. Outdoor unit air outlet block
8. In heating mode indoor unit fan stop
9. In heating mode indoor unit EXV block
H5
Refrigerant shortage fault
System leakage