ARV 6 ALL DC INVERTER T1 50&60HZ Service Manual
25
3.5 Flaring of copper tube
3.5.1 The
burr
of the copper tube
should be removed
before the copper tube is
expanded
3.5.2 It is required to expand the inside diameter at connection area with
Tube expander
3.5.3 The copper pipe connected to the indoor units needs to be expanded by
Expander