ARV 6 ALL DC INVERTER T1 50&60HZ Service Manual
22
3.2 Selection of copper pipe
3.2.1 Please use
seamless red copper pipe
.
3.2.2
Specification
of refrigerant pipe should be selected according to
unit requirement
※
Thickness of copper tube
Specifications
Thickness
(mm)
Weight / length
inch
mm
1m =* Kg
1Kg=* m
1/4
Φ 6.35
0.8
0.124
8.06
3/8
Φ 9.52
0.8
0.195
5.12
1/2
Φ 12.7
0.9
0.297
3.36
5/8
Φ 15.88
1.0
0.416
2.4
3/4
Φ 19.05
1.0
0.505
1.98
7/8
Φ 22.22
1.2
0.706
1.41
1
Φ 25.4
1.2
0.813
1.23
Φ 28.6
1.2
0.92
1.08
Φ 31.8
1.2
1.11
0.9
Φ 34.9
1.3
1.223
0.817
Φ 38.1
1.4
1.438
0.695
difficult oil return
abnormal air exhaust
difficult oil return
(
insufficient
air velocity)
Too long
Too thick
blocked
compressor
blocked
compressor
abnormal air exhaust
Summary of Contents for ARV Series
Page 71: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 71...
Page 88: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 88...
Page 114: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 114...
Page 118: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 118...
Page 131: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 131...
Page 150: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ 150 Symbol Description...
Page 151: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ 151...
Page 172: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 172...