MegaLife
ARV OUTDOOR UNIT
–
ARV 6 ALL DC INVERTER T1 50&60HZ Service Manual
51
1. Preparatory work
1.1 Inspection and confirmation
Confirm that
refrigeration piping and communication
wire of indoor and outdoor units
have been connected to the same refrigeration system in order avoid unnecessary
malfunctions.
Confirm
power voltage
is within ±15% rated voltage.
Confirm that the
power wire and control wire
are correctly connected
Confirm
wired controller
is properly connected.
Confirm all units have passed
nitrogen
pressure-keeping test for
24 hours
.
Confirm the system has been carried out
vacuum
drying
and charged with refrigeration
as required.
1.2 Preparation before start up
Turn on power switches of outdoor unit in advance, and keep connected for
a minimum
of 6 hours
to ensure refrigerant oil is sufficiently heated.
Turn on all valves
. If valves are not fully open unit may be damaged.
All dial
switches
of indoor / outdoor units have been
set according to the technical
requirements.
Summary of Contents for ARV Series
Page 71: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 71...
Page 88: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 88...
Page 114: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 114...
Page 118: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 118...
Page 131: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 131...
Page 150: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ 150 Symbol Description...
Page 151: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ 151...
Page 172: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 172...