ARV OUTDOOR UNIT
–
ARV 6 ALL DC INVERTER T1 50&60HZ Service Manual
158
NO
↓
Condenser dirty block?
→
Clean
NO
↓
Pressure sensor is abnormal?
→
Replace sensor
NO
↓
Discharge temperature and Driver
modular temperature is too high?
→
Yes
↓
Lack of refrigerant?
→
Add refrigerant
NO
↓
NO
↓
Lack of frozen oil?
→
Add frozen oil
NO
↓
Contact the manufacturer's Technician