MegaLife
ARV OUTDOOR UNIT
–
ARV 6 ALL DC INVERTER T1 50&60HZ Service Manual
165
6. Appendix
Relation between temperature sensor of compressor and resistance
R25=50KΩ±1%
B25/50=3950K ±1%
T [
℃
]
Rmin [KΩ]
Rnom [KΩ]
Rmax [KΩ]
-20
449.9
464.7
479.9
-19
425.7
439.5
453.6
-18
402.9
415.7
428.8
-17
381.5
393.4
405.6
-16
361.3
372.3
383.6
-15
342.2
352.5
363.0
-14
324.3
333.9
343.7
-13
307.5
316.4
325.5
-12
291.5
299.8
308.3
-11
276.6
284.3
292.2
-10
262.4
269.6
276.9
-9
249.0
255.7
262.5
-8
236.5
242.7
249.0
-7
224.5
230.3
236.2
-6
213.3
218.7
224.2
-5
202.7
207.7
212.8