ARV 6 ALL DC INVERTER T1 50&60HZ Service Manual
138
2.2 Pressure sensor failure (2)
Code
Definition
Possible reason for error code
F1
【
P
d
】
High pressure sensor failure
1. High pressure sensor failure
2. High pressure sensor connection
is incorrect
3.
Outdoor unit’s main PCB failure
F4
【
P
s
】
Low pressure sensor failure
1. Low pressure sensor failure
2. The connection between sensor
and outdoor PCB incorrect
3.
Outdoor unit’s main PCB failure
2.3 Pressure abnormal (4)
Code
Definition
Possible reason for error code
F3
【
P
d
】
High pressure too high
1. Exhaust pipe or condenser pipe block
2. Condenser dirty
3. Outdoor unit fan stop or low speed
4. Refrigerant overcharge
F6
【
P
s
】
Low pressure too low
1. Indoor unit fan stop or low speed
2. Evaporator dirty
3. Indoor EXV full open in cooling mode
(Outdoor EXV full open in heating mode)
4. Lack refrigerant
5. The pipe between evaporator and suction
port block
Summary of Contents for ARV Series
Page 71: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 71...
Page 88: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 88...
Page 114: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 114...
Page 118: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 118...
Page 131: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 131...
Page 150: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ 150 Symbol Description...
Page 151: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ 151...
Page 172: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 172...