ARV 6 ALL DC INVERTER T1 50&60HZ Service Manual
28
3.7 Oil Trap
When the Vertical
height
between indoor and outdoor units more than
8 or 10 meters
,
ensure the Refrigeration
oil return to
compressor
smoothly, the
oil trap is necessary
O il Tra p
1#
2#
3#
4#
5#
Bra n c h Pip e
( A FG - * B )
Liquid Side
G a s Side
8~
10
m
8~
10
m
C
A
R