MegaLife
ARV OUTDOOR UNIT
–
ARV 6 ALL DC INVERTER T1 50&60HZ Service Manual
137
outdoor
and
indoor units
indoor unit and outdoor unit disconnect,
short circuit or incorrect
2.
Indoor unit’s main power failed
3.
Indoor unit’s PCB failure
4. Outdoor unit
’s main PCB failure
J3
Communication
failure
between
main PCB
and
compressor drive
module
1. The connection between driving module
and main PCB failure
2. The communication part of outdoor unit
control PCB failure
3. Compressor driving module failure
4. Compressor failure
5. Main PCB failure
J4
Communication
failure
between
main PCB
and
fan motor drive
module
1. DC fan motor drive module failure
2. DC fan motor failure
3. Supply voltage exceed limit
4. Main PCB failure