Object value at shortfall
ON
OFF
Setting the polarity
Send at Day
Send nothing
only ON
only OFF
ON und OFF
Transmit filter during daytime
operation
Send at Night
Send nothing
only ON
only OFF
ON und OFF
Transmit filter during
nighttime operation
Table 18: Settings - Brightness
In the menu "Brightness" the transmission conditions for the measured brightness value can be
defined. The measured brightness value can be transmitted both at a certain change and at certain
intervals.
In addition, a threshold value switch can be set for a specific brightness. This can be set with a
hysteresis that avoids too frequent switching. The interplay of hysteresis and threshold value is
illustrated in the following diagram:
Figure 21: Hysteresis - threshold switch
The polarity and the transmission conditions can be defined as desired with the other parameters.
Both, the polarity and a transmit filter can be set.
The following table shows the relevant communication objects:
Number
Name
Length
Usage
66
Threshold switch
1 Bit
sends the set value at exceedance/shortfall
67
Status brightness value
2 Byte
measured brightness value
Table 19: Communication objects - Brightness