4.3 Alarm
The following figure shows the settings for the alarm function:
Figure 17: Settings - Alarm function
The following table shows the parameter settings for alarm detection:
ETS-Text
Dynamic range
[Default value]
Comment
Active sensors
----
1---
-2
—
.
.
.
-234
1234
Setting which sensors are active for
alarm detection
Number of sensors per type (3 or 4)!
Release sensitivity for
Day/Night
1-6
[3 (Day), 2 (Night)]
Adjustment of sensitivity for triggering
the alarm in standby mode (no motion
detected)