Technical Manual Presence Detector SCN-P/G360XX.02
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-
880 •
Fax: +49-2263-4588
• [email protected] • www.mdt.de
9
9
Constant light
(only for SCN-x360Kx.02)
In this menu, all settings for controlling the Constant light function are made. The presence
detector can control up to 3 light bands, which are divided into wall, centre and window
sections. An intelligent proportional master/slave control ensures that the presence detector
regulates the entire room to the same brightness and thus compensates for external
influences such as sunlight..
Logic
Up to 4 logic blocks can be activated in this menu. Within one logic block, settings can be
made between the functions AND/OR/XOR, different output objects, sending conditions and
up to two internal inputs or four external inputs.
2.6 Settings in the ETS-Software
Selection at the product database
Manufacturer: MDT Technologies
Product family: Presence detector
Product type: Ceiling
Medium Type: Twisted Pair (TP)
Product name:: dependent of the used type, e.g.SCN-P360K4.02
Order number: dependent of the used type, e.g. SCN-P360K4.02
2.7 Commissioning
After wiring, the allocation of the physical address and the parameterization of every channel follows:
(1)
Connect the interface with the bus, e.g. MDT USB Interface
(2)
Switch on bus voltage
(3)
Press the programming button at the device (red programming LED lights)
(4)
Loading of the physical address out of the ETS-Software by using the interface (red LED goes
off as soon as this process was completed successfully)
(5)
Loading of the application, with requested parameterization
(6)
If the device is enabled you can test the requested functions (also possible by using the ETS-
Software)