Technical Manual Presence Detector SCN-P/G360XX.02
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-
880 •
Fax: +49-2263-4588
• [email protected] • www.mdt.de
34
34
4.6 Brightness
The following picture shows the available settings for brightness detection:
Figure 20: Settings - Brightness
The following table shows the possible settings for this parameter:
ETS-Text
Dynamic range
[Default value]
Comment
Send brightness at change of
not send
10 Lux
–
1200 Lux
[50 Lux]
Minimum rate of change to
send the current brightness
value
Cyclical sending of light value
not used
5s
–
30min
Definition of a fixed time
period after which the current
brightness value is
transmitted
Threshold switch enable at
60Lux
–
1000 Lux
[300 Lux]
Setting of the threshold at
which the threshold switch
switches over = defined
switch-on point
Hysteresis of threshold switch
5 Lux
–
200 Lux
[30 Lux]
Distance between switch-off
and switch-on point
Switch-off point = value for
switching the threshold switch
- Hysteresis
Object value at Day and
exceedance
ON
OFF
Setting the polarity
Object value at Night and
exceedance
ON
OFF
Setting the polarity