Technical Manual Shutter Actuator JAL-0X10X.02
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-
880 • Fax: +49
-2263-4588
• [email protected] • www.mdt.de
28
28
4.2.1 Blinds
If a channel is selected as a blind, the user has a number of options for parameterization. These are
explained in more detail in the following sections.
As soon as the channel is selected as a blind, three communication objects are shown for this channel
as standard.
The following table shows these communication objects:
Number
Name
Length
Usage
23
Blinds up/down
1 Bit
Movement function of the blinds
24
Slats up/down/stop
1 Bit
Adjustment of the slats/ Stopping of the blinds
movement
Table 6: Communication objects Blinds
The communication object "Blinds Up / Down" is used for the moving function of the blind. Note that
a logical "0" starts the upward movement and a logical "1" starts the downward movement. This
configuration is set by KNX as standard and regulates a uniform communication between KNX
devices
The communication object "slats adjustment / stop" is used for adjusting the slats. Simultaneously,
when this communication object is activated, an active movement function is stopped.
4.2.2 Shutter
The user also has a number of parameterization options available for the shutter function. The blind
function and the shutter function are almost identical, but the parameters for the slats are missing in
the shutter function.
When the channel is selected as blinds, three communication objects are shown for this channel as
standard.
The following table shows these communication objects:
Number
Name
Length
Usage
23
Shutter up/down
1 Bit
Movement function of the shutter
24
Short term operation/Stop
1 Bit
Starts the short term operation /
Is only displayed when activated /
Stops active up-/down movement
25
Stop
1 Bit
Stopping the shutter movement
Table 7: Communication objects Shutter
The communication object "Shutter up/down" is used for the movement function of the shutters.
Note that a logical "0" starts the upward movement and a logical "1" starts the downward movement.
With the object for short term operation, the shutter can be moved in small steps in order to
approach exact positions.
The communication object "Stop" is used to stop an active movement. When this communication
object is activated, whether with "0" or "1", the active movement is stopped.