Technical Manual Shutter Actuator JAL-0X10X.02
MDT technologies GmbH, Geschäftsbereich Gebäudeautomation - Tel.: +49-2263-880
•
Fax: +49-2263-4588
•
E-Mail:[email protected]
•
www.mdtautomation.de
14
14
13
Central function
Block Clouding/
Enable Clouding
DPT 1.003/
DPT 1.001
receive
Actuator reacts to
incoming-telegram
Visu,
Timeswitch,
Push button
Communication object can be
activated in the menu
Clouding
basic settings
and is used to
activate or block the clouding
function.
14
Central function
Clouding diagnosis
DPT 16.000
send
Actuator sends
status
Visu, Diagnosis,
Commissioning
Communication object can be
activated in the menu
Clouding
basic settings
and is used for
diagnostis function.
Objects for Automatic function:
15-
18
Automatic A
Automatic position 1-4
DPT 1.017
receive
Actuator reacts to
incoming-telegram
Push buttons,
Visu...
for manual
control
Actuator calls the saved values
in the individual channels for
this automatic position.
Enables the adjustment of
absolute values via 1 Bit
19-
22
Automatic B
Automatic position 1-4
DPT 1.017
receive
Actuator reacts to
incoming-telegram
Push buttons,
Visu...
for manual
control
Actuator calls the saved values
in the individual channels for
this automatic position.
Enables the adjustment of
absolute values via 1 Bit
Objects per channel:
23
Channel A
Blinds up/down
DPT 1.007
receive
Actuator reacts to
incoming-telegram
Push buttons,
Visu...
for manual
control
This communication object
appears in the
operating mode
"Blinds"
and allows the control
of the basic functions
up/down
which are usually linked to all
desired operating keys.
(= Basic function for blinds)