Technical Manual Shutter Actuator JAL-0X10X.02
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-
880 • Fax: +49
-2263-4588
• [email protected] • www.mdt.de
50
50
4.9.2 Automatic blocks
In order to use the automatic function, the corresponding blocks (A and / or B) have to be activated
in the "General settings" menu.
The following figure shows the possible settings for the automatic blocks:
Figure 16: Automatic blocks
If an automatic block is activated, the communication objects belonging to the activated block are
displayed. Each block contains 4 communication objects, one for the corresponding automatic
position.
The communication objects are shown in the following table:
Number
Name
Function
Length
Usage
15
Automatic A
Automatic position 1
1 Bit
Call of automatic position 1 in Block A
16
Automatic A
Automatic position 2
1 Bit
Call of automatic position 2 in Block A
17
Automatic A
Automatic position 3
1 Bit
Call of automatic position 3 in Block A
18
Automatic A
Automatic position 4
1 Bit
Call of automatic position 4 in Block A
19
Automatic B
Automatic position 1
1 Bit
Call of automatic position 1 in Block B
20
Automatic B
Automatic position 2
1 Bit
Call of automatic position 2 in Block B
21
Automatic B
Automatic position 3
1 Bit
Call of automatic position 3 in Block B
22
Automatic B
Automatic position 4
1 Bit
Call of automatic position 4 in Block B
Table 21: Communication objects - Automatic function
The communication objects with the size 1 bit can then be assigned to the group addresses as
desired.
By calling one of the 8 communication objects, the stored values for this automatic function are then
executed. When a communication object is called, it is possible to simultaneously move all the
channels of the actuator to the parameterized value or only a single channel. This depends on the
parameterization which was made for the individual channels in the sub menu for the automatic
function. In order to move several channels simultaneously to certain values, the same automatic
blocks have to be selected for these channels and the desired values for the same automatic position
have to be stored.