The following table shows the possible settings:
ETS-Text
Dynamic range
[Default value]
Comment
Startup time
2-60s
[2s]
Sets the time between restart
and functional start-up of the
device
Manual operation
active
blocked
lockable over objekt
Release of manual operation.
active
: manual operation
possible
blocked
: no manual operation
possible
lockable over objekt:
Manual
operation can be disabled /
enabled via object
Eco mode, switch LED´s off
after:
not active
30s-60min
Setting whether the LEDs
should be switched off after
the set time
Se d Operatio y li
0-30.000min
[0 = not active]
Setting whether a cyclic in-
operation telegram is to be
sent
Overwrite learned scenes
Retain learned scenes
Load parameter
Setting whether the teached-in
scenes should be retained after
programming or the parameter
values should be reloaded after
each programming.
Automatic clouding
not active
active
Displays the menu for
automatic clouding.
Automatic Block A
not active
active
Displays the objects for
automatic block A.
See also: 4.9
Automatic Block B
not active
active
Displays the objects for
automatic block B.
See also: 4.9
Table 3: Parameter - General Settings
The following table shows the related communication objects:
Number
Name
Length
Usage
5
Operation
1 Bit
Cyclic sending of operation telegram
6
Block manual control
1 Bit
Blocking the manual control when blocking via
object active
Table 4: Communication objects - General Settings