Technical Manual Shutter Actuator JAL-0X10X.02
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-
880 • Fax: +49
-2263-4588
• [email protected] • www.mdt.de
66
66
Automatic switching of summertime
An automatic change-over of the summer time can be set here (from V3.2). The setting was always
active before. In countries without summer time it makes sense to deactivate this function.
Location determination
The location determination is required to calculate the sun position for the object.
Diagnostic objekt
The diagnostic object can be used as a status for visualizations or for commissioning/diagnostics. It
includes information about the readiness of clouding, threshold, azimuth and elevation (see also
4.13.3). The diagnostic object is constructed as follows:
M1 S1 A150 E30
Mx
Display of clouding mode; bit coded:
Bit 1:
0 = Clouding not ready, 1 = Clouding ready
Bit 2:
0 = Clouding not blocked, 1 = Clouding blocked
Bit 3:
0 = no outside temperature block, 1 = outside temperature block active
Example:
M6-> in binary form: 110 -> Clouding blocked and temperature block active
Sx
Indication whether threshold 1/2 is exceeded
S0:
No threshold is exceeded
S1:
Brightness threshold 1 is exceeded
S2:
Brightness threshold 2 is exceeded
Axxx
Output of the azimuth (sun angle) of the sun in degrees
Exx
Output of the elevation (sun height) of the sun in degrees
Appears the message
ERR: Date
, no value for date / time was received.
The following table shows the general communication objects for clouding:
Number
Function
Length
Usage
7
Time
3 Byte
Presetting the time
7
Date/Time
8 Byte
Presetting Date and Time
8
Date
3 Byte
Presetting the Date
9
Brightness 1
2 Byte
Preseting the brightness value 1
9
Brightness 1
1 Bit
Preset that the brightness threshold 1 has been
exceeded
10
Brightness 2
2 Byte
Preseting the brightness value 2
10
Brightness 2
1 Bit
Preset that the brightness threshold 2 has been
exceeded
11
Brightness 3
2 Byte
Preseting the brightness value 3
12
Outside temperature
2 Byte
Presetting the outside temperature
12
Outside temperature
threshold
1 Bit
Preset that the outside temperature threshold
has been exceeded
13
Block clouding
1 Bit
Blocking of clouding
13
Enable clouding
1 Bit
Activation of clouding
14
Couding diagnosis
14 Byte
Diagnosis object of clouding
Table 33: General communication objects - Clouding