Technical Manual Shutter Actuator JAL-0X10X.02
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-
880 • Fax: +49
-2263-4588
• [email protected] • www.mdt.de
37
37
4.4.3 1Bit object for
Move to p
osition
The following table shows the possible settings for this parameter:
ETS-Text
Dynamic range
[default value]
Comment
1 bit object fo
r „
Move to
p
ositio
not active
active
Activation of the function
„
Move
to p
ositio
via 1 bit
Action at value = 1
always
only if shutter is up
only if shutter is down
Action for the
„
command
Position of blinds/
position of slats/
position of shutter
0-100%
[50%]
Absolute position to be
approached by activation via a
„
command
Action at value = 0
(only if position
valid)
no function
move up
move down
Action for the
„
0
command
Table 10: Setting options - Move to position via 1Bit object
With the function
„
1bit object for move to p
ositio
it is possible to approach fixed positions via a
simple 1bit object. Additional conditions can be programmed when this action should be executed. In
contrast to the automatic function, the action only applies to one channel and can thus be adapted
individually for each channel.
The "Action at value = 1" parameter can be used to determine whether the absolute position should
be called at any position, or only in one of the two end positions.
With the "Action at value = 0" it is possible to set whether the channel should return to an end
position or remain in the approached position after the procedure.
The "action at value = 0" is only executed if the current shutter position is still the same as the set
position. If, in the meantime, the shutters are moved to a different value, the action is not executed.
The "1 bit object 'Move to position' " function can still be executed even when the window is open or
tilted.