4.6 Central Objects
The "central objects" parameter can be used to define individually for each channel whether and
which objects this channel should react to.
Figure 10: Central objects
The following table shows the possible settings for this parameter:
ETS-Text
Dynamic range
[default value]
Comment
Central objects
not active
only Up
only Down
only Up/Down
only absolute position
only absolute position
and Up
only absolute position
and Dopwn
absolute position and
Up/Down
Determine which central objects
this channel should react to
Table 14: Setting options - Central objects
The central communication objects are permanently displayed even if the parameter "central
objects" has not been activated in any channel. The central objects are indicated with "Central
function" and are at the top of the list of communication objects.
Number
Name
Length
Usage
0
Rollladen Auf/Ab
1 Bit
Driving function for all channels
1
Slats adjustment/Stop
1 Bit
Slats adjustment/Stop function for all blind
channels
2
Stop
1 Bit
Stop function for all channels
3
absolute position
1 Byte
Absolute hight position command for all channels
4
absolute position of slats
1 Byte
Absolute position command for the slats for all
blind channels
5
operation
1 Bit
Se ds a i operatio telegra
Table 15: Central communication objects