3.3 Communication Objects per Channel
According to the setting, different objects are shown for this channel. The following sections show
the communication objects for each state. The numbers of the communication objects are always
shown for channel A. At channel B, the numbers would be increased by 20, at channel C by 40 and so
on.
3.3.1 Communication objects
–
switching (1 Bit)
If a ha el is sele ted as „s it hi g Bit , the follo i g o je ts, depe di g to the
parameterization, will be shown:
Figure 5
: Co
u i atio o je ts „s it hi g 1Bit
The control value is executed as 1 Bit value. Furthermore additional objects, depending to the
parameterization, are available.
The chart shows the available objects:
Nr.
Function
Usage
0
Control Value
Input for external control value
In, Write
2
Block
blocks the channel
In, Write
3
State control value
sends the current value of the control
value
Out, Read
4
Message emergency
mode
indicates an active emergency mode
Out, Read
5
Forced position
activates the forced position
In, Write
5
Dew point alarm
activates the dew point alarm
In, Write
Table 3
: Co
u i atio o je ts „s it hi g 1Bit
3.3.2 Communication objects
–
continuous (1 Byte)
If
a ha el is sele ted as „ o ti uous B te , the follo i g o je ts, depe di g to the
parameterization, are shown:
Figure 6
: Co
u i atio o je ts „ o ti uous 1B te
The control value is executed as 1 Byte value. Furthermore additional objects, depending to the
parameterization, are available.